Assessing the Performance of ROCOF Relay for Anti-Islanding Protection of Distributed Generation Under Subcritical Region of Power Imbalance

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
1
1
1
1

Citation Types

0
7
0

Year Published

2021
2021
2024
2024

Publication Types

Select...
8

Relationship

0
8

Authors

Journals

citations
Cited by 30 publications
(7 citation statements)
references
References 25 publications
0
7
0
Order By: Relevance
“…As can be observed in Figure 15, the ER G83 setting failed to detect 32 out of 100 cases in less than 2 s whereas the adjustment calculated using BEM only failed to detect 15 out of 100 cases. These cases correspond to scenarios with ∆𝑃 10%, falling within the well-known NDZ for this type of IDM [15,35,56]. Furthermore, the detection time in all cases was shorter for the adjustment achieved using BEM compared to ER G83.…”
Section: Stability Against Tranmission System Disturbances Analysismentioning
confidence: 62%
See 2 more Smart Citations
“…As can be observed in Figure 15, the ER G83 setting failed to detect 32 out of 100 cases in less than 2 s whereas the adjustment calculated using BEM only failed to detect 15 out of 100 cases. These cases correspond to scenarios with ∆𝑃 10%, falling within the well-known NDZ for this type of IDM [15,35,56]. Furthermore, the detection time in all cases was shorter for the adjustment achieved using BEM compared to ER G83.…”
Section: Stability Against Tranmission System Disturbances Analysismentioning
confidence: 62%
“…A notable increase in detection time was observed as the active and rea tive power imbalances in the island approached zero. This is where it is expected to b found for RoCoF and FVT NDZ [15,35]. Furthermore, the stability of the minimal entrop settings, presented in Figure 7, was assessed using the validation distribution faults d taset detailed in Table 2.…”
Section: Entropy Surface Exploration Minimal Entropy Settings and Val...mentioning
confidence: 93%
See 1 more Smart Citation
“…On the other hand, in 24 the blend of ROCOF and ROCOV relay produced a smaller NDZ than the combination of OUF and OUV. Moreover, a comprehensive computational analysis was carried out in 101 to regulate the upper bound of the ROCOFs NDZ.…”
Section: Islanding Detection Methodsmentioning
confidence: 99%
“…Due to the high probability of misoperations that can occur during events unrelated to islanding, in some countries, the Vector Shift is no longer used in island detection. This criterion has been replaced by other algorithms, usually ROCOF [22] - [27].…”
Section: The Impact Of External Disturbances On Vector Shift Criterio...mentioning
confidence: 99%