“…Those proposed values are valid for the assumption of global emission level of 0.50 in each voltage level and the transfer coefficients of 1.0 between the MV and LV networks, and 0.90 between the HV and MV networks [1]. Reference [20] also suggests the planning level values (P st ) for the HV network as 1.2 (at 95% of the time) and 1.4 (at 99% of the time), exceeding the compatibility level of 1.0.…”
Section: Estimation Of Planning Level Values Of Flickermentioning
confidence: 99%
“…Those proposed values are valid for the assumption of global emission level of 0.50 in each voltage level and the transfer coefficients of 1.0 between the MV and LV networks, and 0.90 between the HV and MV networks [1]. Reference [20] also suggests the planning level values (P st ) for the HV network as 1.2 (at 95% of the time) and 1.4 (at 99% of the time), exceeding the compatibility level of 1.0.…”
Section: Estimation Of Planning Level Values Of Flickermentioning