2010
DOI: 10.5207/jieie.2010.24.10.136
|View full text |Cite
|
Sign up to set email alerts
|

Breakdown Characteristics of Dry Air under 170[kV] GIB

Abstract: In this paper, we studied the dielectric breakdown voltage characteristics by the AC withstand voltage test on using green insulation dry air instead of SF6 insulation gas used in the GIB (gas insulated bus) of 362 kV GIS (gas insulated switchgear). The AC withstand voltage test applied to the standard KEPCO's 362 kV GIB with dry air insulation, and the equivalence of dielectric breakdown voltage for dry air and SF6 gas were examined, and the empirical formulas of dielectric breakdown voltage for dry air were … Show more

Help me understand this report

This publication either has no citations yet, or we are still processing them

Set email alert for when this publication receives citations?