“…Assuming a temperature difference between the supply air and room air of 25°F, the total delivered energy that 40 CFM can deliver is 1,084 Btu/h. This value is approximately 7% of the total peak load of the house (Stecher and Imm 2013), most likely inadequate for sufficient occupant comfort if used as the sole source of space conditioning. However, if the conditioned ventilation supply air were delivered to only the three bedrooms of the house, the difference between the delivered load and the required load would be halved.…”