Abstract:Generally, Central Asia is typical for regions with strong solar radiation and various natural cooling sources. The heat gain from the building envelope accounts for a large part of the cooling load there. Thus, the pipe-embedded envelope is receiving attention as a semi-active system of utilizing natural energy for cooling. In this study, the performance of the pipe-embedded envelope used in Urumqi is numerically investigated. The energy saving potential regarding evaporative cooling and a ground-source heat exchanger (GSHE) is evaluated over a complete summer. The results show that the built-in pipes can reduce 80% of the solar heat gain through windows, with an effectiveness of around 60%. External windows rather than internal windows should be insulated because the air cavity is cool. With respect to the pipe-embedded wall, it becomes a radiant cooling panel absorbing the heat from the room, with an effectiveness around 83%. The seasonal cooling energy is decreased by 25%-50% in a typical office with a pipe-embedded envelope. Offices with a large window-to-wall ratio are acceptable because natural cooling is employed. GSHE performs the best among the selected sources. The effectiveness of evaporative cooling is also satisfactory, with an energy saving rate of 27%. Overall, the pipe-embedded system is suitable for climatic regions like Urumqi.