Abstract:The control system of a doubly-fed adjustable-speed pumped-storage hydropower plant needs phase-locked loops (PLLs) to obtain the phase angle of grid voltage. The main drawback of a comb-filter-based phase-locked loop (CF-PLL) is the slow dynamic response. This paper presents a modified comb-filter-based phase-locked loop (MCF-PLL) by improving the pole-zero pattern of the comb filter, and gives the parameters' setting method of the controller, based on the discrete model of MCF-PLL. In order to improve the disturbance resistibility of MCF-PLL when the power grid's frequency changes, this paper proposes a frequency-adaptive modified, comb-filter-based, phase-locked loop (FAMCF-PLL) and its digital implementation scheme. Experimental results show that FAMCF-PLL has good steady-state and dynamic performance under distorted grid conditions. Furthermore, FAMCF-PLL can determine the phase angle of the grid voltage, which is locked when it is applied to a doubly-fed adjustable-speed pumped-storage hydropower experimental platform.