Flue gas after wet desulfurization contains a large quantity of water vapor,
as well as a small amount of fine particulate matter, acid and other
pollutants. Direct emissions will cause haze and environmental pollution.
Flue gas condenser can effectively recover latent heat of vaporization and
remove these pollutants. However, the traditional flue gas condenser has
disadvantages such as large volume, low heat exchange efficiency and easy
blockage. To overcome these problems, a new type narrow gap heat exchanger,
which is easy to detach and clean, is proposed. Then, the flue gas
condensation characteristic is experimentally investigated. The factors
including velocity and temperature of flue gas, flow and temperature of
cooling water are studied on heat transfer coefficient and the condensation
rate. The results indicate that the overall heat transfer coefficient is 7
times of convection heat transfer coefficient, and the condensation rate can
reach more than 60%. As the cooling water temperature increases, the
condensation rate and condensation heat transfer coefficient gradually
decrease. With the increasing of the flue gas velocity, condensation rate
gradually decreases and condensation heat transfer coefficient gradually
increases. Finally, the dimensionless correlation of Nu number is carried
out, and the error is within 10%.