Abstract:To broaden the database of fire equipment selection and provide the basis for its selection and optimization, a low specific speed centrifugal fire pump with a specific speed of 24.7 was selected as the research object, and the inlet and outlet pressure pulsation and cavitation characteristics under different flow rates were analyzed through experiments. Results show that the head of the fire pump under the design flow rate was 75.68 m, and the efficiency was 36.84%. The dominant frequency of the pressure puls… Show more
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.