Impact of System Strength and HVDC Control Strategies on Distance Protection Performance

Abstract: This paper presents comprehensive studies and tests for evaluating the impact of reduced system strength and different control strategies used by HVDC systems on the performance of distance protection. A Hardware-In-the-Loop (HIL) test setup is established to enable realistic testing of physical relays being used in the system, where simulated voltage and current waveforms are injected into the distance protection relay via an analogue amplifier, and the relay tripping signal is fed back to simulation and reco… Show more