Abstract:In this article, a numerical simulation has been performed to investigate the sub-cooled boiling flow in axisymmetric channels using the two-phase particle model. The equivalent diameter of the channel is 4.38 mm with 365.7 cm in length. The fouling deposited layer is filled with The Nusselt number in the fouling region without fouling deposited could be 50 times higher than that with fouling layer. The heat transfer performance of the channel with thickness of 0.225 mm fouling deposit layer is 5 times larger than that with thickness of 1.55 mm fouling deposit layer. It is also found that the inlet velocity has significant impact on the boiling and total pressure drops along the channel.