To achieve the optimum dust removal performance of an electrostatic
precipitator, the flue gas should be distributed uniformly over its vertical
cross-section. The flow in the upstream flue gas ducts has a significant
influence on the downstream gas distribution in the chamber of the
precipitator. This paper presents the results of homogeneity assessment of
velocity distribution in the ducts and vertical cross-sections of the
electrostatic precipitator of unit A1 at the Nikola Tesla thermal power
plant in Obrenovac. The measurements confirmed that the reconstruction of
the vertical chamber at the front of the precipitator, which was carried out
during the overhaul in 2020, effectively solved the problem of the original
asymmetric arrangement of the vertical flue gas ducts. Nevertheless, the
analysis revealed poor homogeneity of the flow field through the chambers.
Therefore, additional measures must be taken to increase the dust removal
efficiency of the precipitator.