The performance of R-513A and HFC-134a refrigerants is compared in two identical chillers operating at the University of Kansas. R-513A is a more environmentally friendly refrigerant due to its lower global warming potential that can be used as a retrofit replacement for HFC-134a in chillers. This study investigates the performance comparison of transitioning from HFC-134a to R-513A. The chillers have been in operation for two years, and cooling capacity, coefficient of performance, and other operating parameters are compared under similar cooling conditions. Cooling capacities ranged from 100 to 500 kW for both chillers. Overall, the energy consumption and coefficient of performance were statistically the same when operating at the same cooling loads.