Abstract:Abstract:The traditional vapor compression cooling system (VCS) has been criticized for its heavy reliance on electricity consumption and limited control ability of humidity. Compared with the VCS, the liquid desiccant cooling system (LDCS) is more efficient by handling the sensible and latent load separately. The present study investigated the regeneration and corrosion characteristics of an anodized aluminum plate regenerator for the first time. Comparative tests were conducted to present the regeneration an… Show more
“…The Tafel polarization curves for both the 35% LiCl solution and the mixed solution were then obtained at the corresponding setting in the electrochemical work station. The scanning speed for the polarization curve was 1 mV/s, and the scanning range was −0.25V to 0.25V relative to the open circuit potential during the test [28]. Fig.…”
Section: Comparison Of Corrosion Behaviormentioning
“…The Tafel polarization curves for both the 35% LiCl solution and the mixed solution were then obtained at the corresponding setting in the electrochemical work station. The scanning speed for the polarization curve was 1 mV/s, and the scanning range was −0.25V to 0.25V relative to the open circuit potential during the test [28]. Fig.…”
Section: Comparison Of Corrosion Behaviormentioning
“…As one of the key components in LDCS, the dehumidifier has been studied both experimentally and numerically in terms of heat and mass transfer performance [7][8][9][10][11].…”
Section: Introductionmentioning
confidence: 99%
“…Therefore, it has drawn more and more attention in recent years [7][8][9] and the present study selected the plate type as the research object. Different types of mathematics models have been developed to describe the heat and mass transfer processes in the internal cooling plate dehumidifier [7][8][9][10][11][12][13][14][15].…”
“…1. Even the stainless steel 304 cannot resist the 4 / 25 corrosion from lithium chloride solution, needless to say the commonly used aluminum and copper [18][19][20][21]. The corrosion on mass transfer component can not only affect the dehumidification/regeneration performance but also reduce the system reliability dramatically.…”
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.