Measurement Verification of a Developed Strategy of Inrush Current Reduction for a Non-Loaded Three-Phase Dy Transformer

Marian Łukaniszyn,
Łukasz Majka,
Bernard Baron
et al.

Abstract: This article presents the measurement verification of a novel strategy for inrush current reduction in an unloaded three-phase Dy transformer. The strategy combines appropriate pre-magnetization of transformer cores with an original control switching system using initial phase values of the supply voltage as control variables. Measurements were recorded for primary voltages and currents as well as secondary voltages during transient states at start-up under no-load conditions. Various inrush scenarios were exa… Show more