“…Using the incorrect parameters for the dead band, droop, and ramp rate constraints can lead to significant incorrect frequency response and as a result, exhibiting frequency mismatch between simulation results and measurement values. 3,18,33 Simulation tests prove that system responses are much less sensitive to the values of other turbine-governor parameters such as time constants. 21 Therefore, in this article, only the key parameters which dominate the measured responses are selected for extraction in the validation process, and other parameters are only considered in the models with the known parameters values.…”