In the present work the dynamic behavior of a plate heat exchanger (PHE) (single pass counter current consists of 24 plates) studied experimentally and theoretically to control the system. Different control strategies; conventional feedback control, classical fuzzy logic control, artificial neural network (NARMA-L2) control and PID fuzzy logic control were implemented to control the outlet cold water temperature. A step change was carried in the hot water flow rate which was considered as a manipulated variable. The experimental heat transfer measurements of the PHE showed that the overall heat transfer coefficient (U) is related to the hot water flow rate (m h ) by a correlation having the form: