In new and refurbished buildings, different energy sources are usually exploited to reach the Near Zero Energy Building target. Heat pumps and renewables are the most common adopted technologies. The coupling of the different components with a control logic conceived to exploit all energy contributions causes an implied design complexity. In this paper, two case studies were reported regarding the use of multisource heat pump systems: as main novelties, the correct design of the solar field (thermal or photovoltaic/thermal) in relation with the other sources (ground heat exchangers, ventilation heat recovery) for a given building and climate was reported in order to balance the energy drawn and injected into the ground around the year, and to attempt to reach the independency from the electric grid. Moreover, the relatively complex (compared to conventional heating or cooling) system controlling for multisource heat pump plants was simulated. The paper reported on the design of the plant, of the control logic, and the energy performance of two original multisource heat pump systems by means of dynamic simulation. In one case, real measured data were available as well. Very high primary energy ratios were obtained due to suitable control logics of the multisource plants, around 1.4 (based on measured data) and 4.7 (based on simulated data) for the first and second case, respectively. As a consequence, non-renewable primary energy consumptions of 37 and 3.9 kWh m−2 y−1 were determined, respectively.