“…For equal time constants and a small delay (L/Tx = 0.1), the value of TRopt for step load changes is 1.7P" or 2.2PU, depending on the location of the disturbance, compared to 0.8PU when there is only one time constant. These high values of TR/PU are similar to those recommended for processes with two large and one small time constant (Hazebrock and van der Waerden, 1950, Harriott, 1964, Weber and Bhalodia, 1979), since the frequency response near the critical frequency is quite similar when the delay or the third time constant is much smaller than the other lags. Using half the maximum gain for these systems does not give much phase Table I.…”