This thesis introduces a new method especially designed to control the instantaneous power in voltage sourced converters operating under unbalanced conditions, including positive, negative and zero sequence content. A transformation technique, labelled mno transformation, was developed to enable the decomposition of the total instantaneous power flowing on three-phase transmission topologies into constant and oscillating terms. It is applied to three-wire and four-wire schemes, especially accommodating zero sequence unlike previous approaches.