Partial Discharge Investigation of a Power Transformer Using Wireless Wideband Radio-Frequency Measurements

Abstract: The remote detection of a transformer internal partial discharge (PD) has been demonstrated using mobile wideband radio-frequency receiving equipment. The PD is externally detectable due to coupling within the transformer tank, causing impulsive signals to be radiated from external connections. A wideband direction-finding technique using a four-antenna array has shown the source of the radiation to be the tertiary winding connections; the radiated impulse has characteristics typical of this method of emission… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
2
2
1

Citation Types

0
43
0
2

Year Published

2010
2010
2020
2020

Publication Types

Select...
7
1
1

Relationship

0
9

Authors

Journals

citations
Cited by 69 publications
(45 citation statements)
references
References 4 publications
0
43
0
2
Order By: Relevance
“…As shown in Figure 3, projection of the antenna array in xoy plane is Y-shape, and A4' is the projection of A4. Assuming that PD source is at the (20,10,3), the time delay sequence can be calculated to be (27.01, 37.94, 15.20) T (unit: ns), substitute the time delay sequence to the localization equations, the assumed location can be accurately solved.…”
Section: Quantitative Analysis Of the Influence Of Antenna Array Arramentioning
confidence: 99%
See 1 more Smart Citation
“…As shown in Figure 3, projection of the antenna array in xoy plane is Y-shape, and A4' is the projection of A4. Assuming that PD source is at the (20,10,3), the time delay sequence can be calculated to be (27.01, 37.94, 15.20) T (unit: ns), substitute the time delay sequence to the localization equations, the assumed location can be accurately solved.…”
Section: Quantitative Analysis Of the Influence Of Antenna Array Arramentioning
confidence: 99%
“…Now we compare the localization error caused by error of wave head time of the UHF signal received by 1 st antenna at different height of the 4 th antenna, when the sampling rate is 1.5GHz. Assuming that PD source is at (20,10,3), the localization results are shown in Table.2.…”
Section: Quantitative Analysis Of the Influence Of Antenna Array Arramentioning
confidence: 99%
“…전 세계적으로 예방진단기술을 전력용 변 압기에 적용하기위하여 연구가 활발히 진행되고 있 으며 [1][2][3][4][5], 최근에는 극초단파신호 (ultra high frequency, UHF)를 이용한 부분방전 검출기술이 변 a. Corresponding author; juhjun@kepco.co.kr 압기 고장예방에 적용되고 있다 [6,7] …”
Section: 서 론 1)unclassified
“…Partial discharges (PD) are well known as a source of insulation degradation and the major sources for insulation failure in power transformers, which play important role in electric power system [1,2]. The capital cost of a power transformer is relatively high and economic penalty due to transformer failure and consequent outage is remarkable.…”
Section: Introductionmentioning
confidence: 99%