2008
DOI: 10.1541/ieejias.128.354
|View full text |Cite
|
Sign up to set email alerts
|

Performance of the .+-.80MVA GCT STATCOM Under Commercial Operation

Abstract: This paper presents a newly developed an 80 MVA GCT STATCOM for the Kanzaki substation of the Kansai Electric Power Co., Inc. The commercial operation was started in June, 2004. The main purpose of the STATCOM is to maintain voltage during single circuit connection of source to the substation resulting from an AC system fault in order not to break down load system of the substation. The developed STATCOM has three distinctive features: (1) a high-efficient, compact and AC filter-less system using multistage th… Show more