“…Additionally, the GSC CB of PV arrays DGSs using PI control [99], adaptive PI control [100] and LBAC [103] offers lower settling times, that is, 0.09, 0.074 and 0.02 s, respectively (Figure 14a) than those achieved with the PI [68], dual dq theory [69], SOS‐PI [72] and GWO‐PI [72] control techniques for the WTs DGSs, that is, 0.2, 0.9, 1.51 and 1.21 s, respectively (Figure 11c). Similarly, the GSC CB of PV arrays systems implemented using FLC [104] and PR control [110] respectively presents much lower THDs of 0.26% and 0.23% (Figure 14c) unlike various advanced GSC CBs of WTs DGSs, for example, APRG [73], FIR [74], MPC [79] etc. as shown in Figure 11a.…”