The Analysis of the Symmetrical Short-Circuit Currents in Backup Power Supply Systems with Low-Power Synchronous Generators

Abstract: This paper presents an analysis of the short-circuit currents of a synchronous generator with a rated power of 16 kVA. For this purpose, the authors carried out measurements of real short-circuit currents during laboratory tests. Additionally, a simulation model of the generator was developed according to the individual machines data from the catalog and field calculations in ANSYS Maxwell software. Based on the mentioned research, the authors compared waveforms of the symmetrical short-circuit currents. In th… Show more

Help me understand this report

Search citation statements

Order By: Relevance

Paper Sections

Select...
2
1
1
1

Citation Types

0
5
0

Year Published

2020
2020
2021
2021

Publication Types

Select...
4
1

Relationship

4
1

Authors

Journals

citations
Cited by 5 publications
(5 citation statements)
references
References 15 publications
0
5
0
Order By: Relevance
“…When the short-circuit phenomena occurs in the low-voltage system supplied by the backup generator set, this fault should be recognized by generator as a close. During this fault type, generator states can be highlighted: sub-transient, transient, and steady-state short-circuit as a consequence of phenomena that takes place inside the generator (electromagnetic flux path changes) [21,22]. Depending on the generator construction, short-circuit state values and their time intervals are different [23].…”
Section: The Characteristic Of Low-power Silent Poles Synchronous Generatorsmentioning
confidence: 99%
See 1 more Smart Citation
“…When the short-circuit phenomena occurs in the low-voltage system supplied by the backup generator set, this fault should be recognized by generator as a close. During this fault type, generator states can be highlighted: sub-transient, transient, and steady-state short-circuit as a consequence of phenomena that takes place inside the generator (electromagnetic flux path changes) [21,22]. Depending on the generator construction, short-circuit state values and their time intervals are different [23].…”
Section: The Characteristic Of Low-power Silent Poles Synchronous Generatorsmentioning
confidence: 99%
“…Due to relatively high values of the generators synchronous reactance, the short-circuit current value during steady-state can be even smaller than its rated current (three-phase or three-phase to earth faults). In detail, this issue is described in [21], where the analysis was done.…”
Section: The Characteristic Of Low-power Silent Poles Synchronous Generatorsmentioning
confidence: 99%
“…The measurement system consisted of current clamps (Fluke ac i1000s-measurement range 100 A, 10 mV/A, accuracy 2% of reading ±5 mV), differential voltage probes (Pintek DP-200pro, measurement range 100:1, accuracy ≤ ±2%), and the data acquisition system built on the NI USB-6259 measuring card and NI LabVIEW Signal Express software in ver. 15.0.0 (National Instruments Corp., Austin, TX, USA) [27,28].…”
Section: Laboratory Setupmentioning
confidence: 99%
“…To measure voltage and current signals, voltage probes were used (Pintek DP-200pro, measurement range 100:1, accuracy ≤ ± 2%) along with current probes (Fluke ac i1000smeasurement range 100 A, 10 mV/A, accuracy 2% of reading ± 5 mV). The signals were collected via an NI measurement card and then analyzed in SignalExpress and Matlab [26,27].…”
Section: Laboratory Pst Constructionmentioning
confidence: 99%