The article is devoted to the study of the fire condition of a non-specialized car service, which is widespread mainly in agricultural areas. The assessment of compliance with the fire safety requirements of the protected object was carried out using a deterministic method and based on the calculation of fire risk. The calculation of the fire risk was carried out taking into account the absence of smoke protection at the facility and the non-compliance of the dimensions of doorways with the requirements of regulatory documents on fire safety. Calculations have shown that the value of an individual fire risk is 0,99∙10-7 per year, i.e. does not exceed the standard value (10-6 per year), established by Federal Law No. 123-FZ. Fire safety at the protected object is ensured.