2001
DOI: 10.1080/00038628.2001.9697461
|View full text |Cite
|
Sign up to set email alerts
|

Time to Flashover for Fires in a ‘Bare Cabin’ with Smoke Extraction System

Abstract: Fires in 'cabins' with only the smoke extraction ystem operating were studied. Cabins of length up to lOm, width up to 8m and height up to 5m, with d@erent ventilation conditions under a NFPA t-fire with a cut-off value of5 MW were investigated. Thefire environments due to all the four sets of slow, meduim, fast, and ultra fm P-fires were tested. i'bepre zone model FIREWND was selected as the simulation tool. The total number of simulations was 14,400, including four m k e exhaust rates. The time toflashover w… Show more