A medium power Current Source Converter (CSC) based Active Power Filter (APF) system is designed and implemented to suppress the amplification of low order harmonics at the Medium Voltage (MV) interface bus between the distribution and transmission systems, owing to the presence of large shunt capacitor banks installed only for reactive power compensation. For this purpose, four CSC based APF units designed at 1.0 kV are operated in parallel, and connected to the 31.5 kV MV bus via a specially designed coupling transformer. In each APF module, a specially designed LC-type input filter eliminates the switching ripples, and active damping method embedded into the control software suppresses harmonic frequencies around the natural frequency of the input filter. The resulting system can operate at relatively high frequencies in the range from 2.0 to 3.0 kHz, depending upon which selected harmonics among 5 th , 7 th , 11 th , and 13 th are to be eliminated. Furthermore, in order to reduce the installed capacity of CSCs, Selective Harmonic Amplification Method (SHAM) is applied to the APF system described in the paper. MV APF system has been built as a mobile system for temporary connection to a problematic MV interface bus, until a permanent solution is found for that location in the distribution system.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.