SUMMARYInvestigations were conducted on the VFT (Very Fast Transient) surges that propagate into a 500-kV transformer. The disconnector restriking surge and ground fault surged were discussed. It was regarded that a large part of the surge voltage was applied just at the entrance of the transformer winding for the VFT surges. Thus, an equivalent circuit that models the windings was used for the analysis. The overvoltages that appear between the first winding sections at the entrance of the transformer were computed. The following was established.(1) The overvoltage between the first winding sections becomes greater when the magnitude of the voltage change at the transformer terminal is larger. The overvoltage between the first winding sections is not affected by the magnitude of the transformer terminal voltage. (2) For the disconnectors that are not connected directly to the transformer, the voltage change at the transformer terminal is not so large. (3) In the case of a ground fault at the GIS near the transformer, the voltage change at the transformer terminal is the same as that for a disconnector directly connected to the transformer. (4) In actual GIS, the disconnector that is connected directly to the transformer is not usually used. In this situation, the overvoltages that threaten the transformer insulation will not be generated by the restriking of the disconnectors.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.