Dew point cooling (DPC) is a novel indirect evaporative cooling concept capable of delivering air temperatures approaching the dew point. Coupling this technology with CO2 refrigeration is well suited to minimising transcritical operation when the coefficient of performance (COP) is dramatically reduced in hot climates. A substantial experimental program was conducted to characterise this combination by testing a 20 kW CO2 refrigeration system subject to ambient temperatures above 40 °C. It was demonstrated that DPC operation not only avoided transcritical operation during such weather conditions, but also increased the COP by up to 140% compared to the conventional system. The combination of these technologies was successfully mathematically modelled, from which the optimum condenser inlet air temperature was identified for each condenser temperature. Using this optimum condition, it was possible to maximise the COP for a range of conditions applicable to the psychometric chart. An annual case study for Adelaide, Australia was conducted which demonstrated that optimally coupling DPC with CO2 refrigeration can reduce the annual energy consumption and peak demand by 16% and 47%, respectively, compared to a conventional CO2 booster system. Furthermore, the number of hours of transcritical operation was reduced from 3278 to 27.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.