Internal heat exchangers (IHX) are commonly used to improve the energy performance of vapour compression refrigeration cycles. However, the magnitude of the improvement depends on the refrigerant and operational conditions. This paper experimentally investigates the influence of a high IHX on vapour compression systems. The new low global warming potential refrigerant R516A is assessed as a drop-in replacement to R134a at different medium temperature refrigeration conditions. In the case of a 40% effectiveness IHX, R516A shows the highest cooling capacity (4.8% to 9.1%), and COP (4.9% to 11.6%) increases compared to the situation without this element. It can be concluded that the IHX always benefits the energy performance of the refrigeration system at acceptable compressor discharge temperatures.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.