This paper analyses the impact of conservation by voltage reduction (CVR) on voltage stability margin (VSM) considering transmission and distribution (T&D) systems. VSM is determined by P-V curve analysis using PSSE and GridLAB-D solvers to co-simulate the T&D systems under CVR and No CVR conditions. ZIP loads with profile [ZIP] = [0.4 0.3 0.3] are used to model the load. The paper discusses the counterintuitive result:under CVR, the VSM is reduced. Theoretical justification for the reduced VSM under CVR is the increase in the effective impedance between generation and load and this is proved using an extended 2-bus system. The paper shares T&D co-simulation results with IEEE 9-bus transmission system and a larger 123-bus distribution system and with distributed generation (DG) in unity power factor (UPF) and volt-VAR control (VVC) mode.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.