Performance of a direct evaporative cooler (DEC) was numerically studied at various outdoor and indoor air conditions, with geometric and physical characteristics of it being extracted based on thermal comfort criteria. For this purpose, a mathematical model was utilized based on the equations of mass, momentum, and energy conservation to determine heat and mass transfer characteristics of the system. It is found that the DEC can provide thermal comfort conditions when the outdoor air temperature and relative humidity (RH) are in the range of 27–41 °C and 10–60%, respectively. The findings also revealed that by raising the RH of ambient air, the system will reach the maximum allowed RH faster and hence a smaller heat exchanger can be used when the ambient air has higher RH. Finally, performance of the DEC in a central province of Iran was investigated, and a design guideline was proposed to determine size of the required plate heat exchangers at various operating conditions.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.