Abstract:The aim of energy efficiency is to use less energy to provide the same service. In hospitals, energy efficiency offers a powerful and cost-effective tool to reduce greenhouse gas emissions, fuel consumption, and also running costs. Over a six-month period, the six gas-fired boilers that provide both a hospital's heat and hot water were monitored. Analysis of the data obtained led to several actions being implemented in the hospital boiler room control system to improve the efficiency of the heat production system. Comparative studies were conducted, during similar weather periods, of the performance of the hospital's hot water production system before and after the controls were implemented. Results indicate that the control actions applied proved to be effective. Finally; the paper offers a financial; primary energy saving and CO 2 reduction analysis that points to a 3,434.00 €/week savings in natural gas consumption; and a cut in CO 2 emissions of 20.3 tons/week; as compared to the reference facility.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.