89AbstractThe conventional PID control (linear) is popular control scheme that is used in almost pH control at waste water treatment process. pH model with respect to titration liquid flow rate has been known to be intrinsically difficult and nonlinear, especially when the process is conducted to non-linear range pH reference (pH 4-8), the settling time reach a long time. Therefore in this paper the nonlinear controller with self-tuning PID scheme is performed handle pH by training a neural-network based on backpropagation error signals. The pH process model is combination between CSTR (Continuous Stirred Tank Reactor) linear dynamic with H 3 PO 4 , HF, HCl, H 2 S flow rate and nonlinear static electro neutrality (wiener process model). The simulation result has a good and suitable performance under several tests (set-point and load change). The simulation result show the pH control system can follow the change of pH set-point and load with the average steady state error 0.00034. The settling time achieved at 50 second faster than conventional PID controller scheme.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.