To avoid the needless trip by magnetizing inrush current, the second harmonic component is commonly used for blocking differential relay in power transformers. However, the main problems of the current comparison method are in the very high inrush currents and relatively small fault currents regarding winding short circuits. Also The second harmonic component in fault current is increased in long lines which may blocks the relay operation. This paper describes a method to discriminate internal fault from inrush current and faults with a high second harmonic component by the sum of active power flowing into the transformer from each terminal. The average power is almost negligible for energizing, but an internal fault consumes large amounts of power.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.