More than three HTS cable development and installation projects are proceeded over the world. A 22.9 kV/50 MVA class HTS cable system has been developed in Korea during last 3 years. And the HTS cable system for commercialization will be developed and installed on the real or test power grid within 2 years. Every HTS cable system has to satisfy the fault-current specifications of the power grid in order to protect the cable itself from the fault current. HTS cable composed of HTS tapes has some capacity of enduring the fault current by bypassing the fault-current through its Ag-sheath. But it may not be enough. So, some Cu stabilizer is generally introduced inside the conductor layers and outside the shield layers of HTS cable core for some higher fault current grade. In this paper, the design method of HTS cable with Cu stabilizer will be introduced. And the fault current capacity of HTS cable and its eddy current loss generated from the stabilizer will be calculated. And the impedance change of HTS cable in the fault current state will be calculated.Index Terms-AC loss, fault current, HTS superconducting power cable system stabilizer, quench.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.