Low inertia levels are typical in island power systems due to the relatively small rotational generation. Displacing rotational generation units with static inertia-less PV power results in a significant increase in the frequency volatility. Virtual inertia provided by inverter-storage systems can resolve this issue. However, a low short circuit ratio (SCR) at the point of common coupling together with a fast phase locked loop (PLL) will compromise the response performance of the system. To address this issue, a robust PI controller (RPI) for the inner current-loop of a current fed grid-connected inverter is proposed. The PLL disturbance and grid impedance are incorporated into a single model and recast to a generalized representation of the system, thereby allowing easy tuning of the RPI by the mixed sensitivity H∞ method. The performance of the RPI is compared with that of a PI controller (PI) tuned by the regular loop-shaping method. The results show that when the SCR is above 10, the performance of both controllers is equivalent. However, lowering of the SCR compromises the performance of the system with PI and it becomes underdamped at SCR < 2. On the contrary, the system with the RPI is capable of maintaining the nominal performance throughout the same SCR decrease.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.