In order to choose one elixir from three anti-scaling inhibitors A, B and C that most suits for the circulating cooling water in thermal power plants under certain water condition, we used the dynamic simulation test method in this paper. Under high concentration rate (4.0), we comprehensively analyzed the three elixirs from the factors of their anti-scaling, corrosion and economical performances. According to the results, it was confirmed that elixir B displayed the relevant good properties for the water condition of the power plant. Meantime, the elixir components of the three elixirs were analyzed, and the results showed that all the indexes of them were in conformity with the national standards.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.