Electrical control boxes are common on high vapour cloud hazard sites, and in the case of the Buncefield explosion the ignition source was inside such a box, that was sited in an emergency pump house building. There has, however, been relatively little previous research into this type of ignition mechanism and its effect on the explosion severity. Commercially available electrical control boxes measuring 600 mm high, 400 mm wide and 250 mm deep were used to explore the pressure development, venting processes and flame characteristics of stoichiometric propane/air explosions using aluminium foil and the supplied doors as vent coverings. In some tests, the boxes were empty in order to establish a baseline for the effect of the internal congestion of the boxes. In other tests a congestion array was added. It was found that, in both the empty and congested box tests, the door produced a flat petal shaped flame, which differed drastically from the mushroom flame shape and associated rolling vortex bubble venting that is traditionally observed with large orifice vented explosions.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.