This paper discusses newly developed control strategies of a self‐commutated converter applied to the HVDC system. An upper and lower power‐limited dc voltage control establishes high performance in a two‐terminal HVDC system. A voltage margin method to reverse dc transmission power also is introduced. Even when the communication system is shut down, if required, dc transmission power can be changed with the authors' proposed controls applied to the terminal control. Furthermore, the dc voltage control scheme with two‐stage voltage control characteristic is presented for multiterminal HVDC system use. When one terminal is collapsed, the multiterminal HVDC system can be operated because of the proposed control characteristics.
Simulator studies were carried out to verify the proposed control performance in the two‐terminal HVDC system and successful test results such as power reversal and a terminal start‐up during other terminal operations are shown.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.