a b s t r a c tAn experimental study has been carried out on a water sprayed air flow aimed at cooling the air upstream of a heat exchanger in order to improve the heat transfer. A pilot has been built allowing injecting droplets in air in various conditions while controlling flow rates, temperature and humidity. The emphasis has been put on the spray evaporation resulting in a temperature decrease and humidity increase in the air flow. An actual increase in the heat exchanged (up to 3 times more) for an air initially entering in surrounding conditions (temperature between 293 and 308 K and relative humidity between 47.5% and 19.7%) has been reached when injecting upstream droplets smaller than 25 mm, in an air flow crossing the exchanger. A validation of a numerical study on the heat exchanges in the air flow has been also achieved. Results will be applied for the optimization of the water flow providing the best compromise between heat exchanged and water consumption.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.