A two-storey test rig was used to investigate how an insulated facade would react to the impingement of a simulated room fire. In particular, whether or not a facade insulated with polyurethane foam would promote vertical flame spread. Wooden cribs weighing 40 kg were used as fire sources. One set of tests was run without any steel cladding to study the behaviour of the polyurethane foam alone. In a wall-configuration test as well as under a corner-configuration one limited vertical and horizontal flame propagation were found. The degree of damage was, to some extent, greater under the corner-test conditions than with the wall tests. A ventilated facade construction with the profiled steel cladding fixed to vertilcal support-work was used for the second set of tests. In order to simulate repair conditions, the outer metal cladding was completely removed from the lower 1.5 m of the facade. In both tests a strong chimney-effect behind the cladding was observed. This intensification of the flame impingement led to a flame spread up the top of the facade. The tests indicated that the vertical flame spread would continue unless the method of construction incorporated vertical fire stops.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.