The structure of the induced voltage test model for low frequency transients is described and presented from its components (generator, auxiliary and power transformer). The performed test procedures are perfomed to estimate the model parameters along with the topology of their connection. Finally, the model is implemented in the transient analysis software ATP and a frequency response of the test is obtained. This allows to identify the critical frequencies that cause resonant states and cause overvoltage during the test which facilitates the establishment of application of safety criteria for both operators and the equipment.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.