This report summarises the work by the Task Force to review the accuracy of the ruling span method for conductors operated at high temperatures. The basics of the ruling span approximation method have been examined. The traditional ruling span approach can be used with little or no error for a typical overhead line crossing a rolling terrain to predict sags in suspension spans for conductor operating temperatures in the range of 5@C to 7OOC. Sensitivity studies were performed using conductors "Lapwing" and "Tern" in order to quantify such ruling span assumptions as the effect of the longitudinal swing of suspension and line post insulators on conductor sags at high temperatures, and the effect of the suspension insulator string length on the equalization of conductor tensions in adjacent spans. Significant errors in estimating the sag at conductor temperature above l OOOC may occur if the tension differences are not taken into consideration in line sections consisting of a series of spans of non-equal lengths, It was confirmed that the ruling span method is the most practical way to string conductors in multi-span line sections.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.