The increase of distributed generation units in low voltage distribution grids, stimulated by different mechanisms (mostly economic), like the Energy Performance of Buildings Directive in Europe and the associated nearly-Zero Energy Building concept, stresses indepth research on the possible impacts that such generation may impose on fundamental grid equipment such as distribution transformers.Taking this into consideration, this paper has two main objectives: i) to analyze the impacts of distributed generation on a non-residential building supplied by a dedicated distribution transformer when this building is converted to a nearly-Zero Energy Building; and ii) to develop a Transformer Anti-Aging Protection System (TAAPS) that mitigates existing negative impacts in order to reduce transformer aging.The present study is based on 1-year, 1-min resolution, real electricity demand and weather data and uses the standard IEC 60076-7 (Loading Guide For Oil-immersed Power Transformers) to model the transformer aging. The collected results show that the introduction of distributed generation increases transformer aging and that the proposed protection system (TAAPS) fulfills its objectives preventing the excessive aging. An economic analysis, related with the proposed system, is also provided in this paper.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.