The hot water circulation system in a building is a system which helps prevent Legionella problems whilst ensuring that tenants have access to hot water quickly. Poorly designed or implemented systems not only increase the risk to people’s health and thermal comfort, but even result in an increase in the energy needed for this system to function properly. Results from previous studies showed that the total hot water circulation system loss can be as high as 25 kWh/m2 heated floor area per year. The purpose of this project is to measure the total energy use per year of the hot water circulation system in about 200 multifamily dwellings of different ages to verify that a system loss of 4 kWh/m2, year is a realistic assumption for both newer and older/retrofitted buildings. The preliminary results from the first 134 measurements showed that the assumption of 4 kWh/m2, year is rarely fulfilled. An average energy use of more than three times this is more common, even in newer buildings. Whilst some of the total energy lost is used to heat the buildings, it is not desirable because it is an uncontrolled energy flow.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.
customersupport@researchsolutions.com
10624 S. Eastern Ave., Ste. A-614
Henderson, NV 89052, USA
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.
Copyright © 2024 scite LLC. All rights reserved.
Made with 💙 for researchers
Part of the Research Solutions Family.