In this study, experiments were performed on air heater samples with three different shapes (chevron, wave and dimple type) to reduce theplumes from cooling towers. The tests were conducted for a range of frontal air velocities of 1~3 m/s and water flow rate 0.19~0.33 kg/s. The results showed that the heat transfer rate increased with increasing air velocity or water flow rate. The air-side pressure drop also increased with increasing air velocity. At the same frontal air velocity, the highest heat transfer rate was obtained for the chevron sample (1.5~1.7 times compared to that of the plate sample), followed by the dimple, wave and plate samples. The heat transfer rate per unit power consumption was also 15% larger than that of the dimple sample. On the other hand, there was no noticeable difference between the other samples.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.