This paper proposes a new method of scheduling for optimal placement and sizing of Distribution STATic COMpensator in the radial distribution networks to minimize the power loss. In the proposed method Voltage Stability Index is used to search the optimal placement for installation of DSTATCOM. Optimal size of DSTATCOM is found by using bat algorithm. The feeder loads are varied by linearly from light load to peak load with a step size of 1%. In each load step, the optimal placement and sizing for DSTATCOM are calculated. By using the Curve Fitting Technique, the optimal sizing for DSTATCOM per load level is formulated in the form of generalized equation. The proposed approach will help the Distribution Network Operators to select the DSTATCOM size according to the load changes. To check the feasibility of the proposed method, system has been tested on two standard buses such as IEEE 33 and 69 bus radial distribution systems.Ó 2015 Faculty of Engineering, Ain Shams University. Production and hosting by Elsevier B.V. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.