High-impedance faults (HIFs) in distribution networks may result in fires or electric shocks. However, considerable difficulties exist in HIF detection due to low-resolution measurements and the considerably weaker time-frequency characteristics. This paper presents a novel HIF detection method using synchronized current information. The method consists of two stages. In the first stage, joint key characteristics of the system are extracted with the minimal system prior knowledge to identify the global optimal micro-phase measurement unit (μPMU) placement. In the second stage, the HIF is detected through a multivariate Jensen-Shannon divergence similarity measurement using high-resolution time-synchronized data in μPMUs in a high-noise environment. l 2,1 principal component analysis (PCA), i.e., PCA based on the l 2,1 norm, is applied to an extracted system state and fault features derived from different resolution data in both stages. An economic observability index and HIF criteria are employed to evaluate the performance of placement method and to identify HIFs. Simulation results show that the method can reliably detect HIFs with reasonable detection accuracy in noisy environments.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.