The objective of this contribution was to study the behaviour of new and regenerated insulating oil used in power transformers under the influence of an electric stress. To estimate the degradation rate of the dielectric fluids, one thousand (1000) successive breakdowns were generated according to the IEC 60156 standard. The parameters such as dissipation factor (Tan ), resistivity, total acid number (TAN) and oil water Content were measured and examined following IEC/ISO standards. Good correlations have been obtained between TAN/resistivity and Tan which might provide a "picture" of the fluid condition. The dissolved oxidation products for the two dielectric fluids (after the application of electric breakdowns), was evaluated by infrared spectroscopy (FT-IR). The results obtained indicate that the degradation of the parameters is significant and confirms the influence of an alternative electric field (AC) on the new and regenerated oils. It was also suspected that inhibitors and antioxidants were removed from the oil after regeneration. Their concentration should therefore be monitored and replenished when necessary.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.