A blackout is usually the result of load increasing beyond the transmission capacity of the power system. A collapsing system enters a contingency state before the blackout. This contingency state is characterized by a decline in the bus voltage magnitudes. To avoid blackouts, power systems may start shedding load when a contingency state occurs called under voltage load shedding (UVLS). The success of a UVLS scheme in arresting the contingency state depends on shedding the optimum amount of load at the optimum time and location. This paper proposes a hybrid algorithm based on genetic algorithms (GA) and particle swarm optimization (PSO). The proposed algorithm can be used to find the optimal amount of load shed for systems under stress (overloaded) in smart grids. The proposed algorithm uses the fast voltage stability index (FVSI) to determine the weak buses in the system and then calculates the optimal amount of load shed to recover a collapsing system. The performance analysis shows that the proposed algorithm can improve the voltage profile by 0.022 per units with up to 75% less load shedding and a convergence time that is 53% faster than GA.
scite is a Brooklyn-based organization that helps researchers better discover and understand research articles through Smart Citations–citations that display the context of the citation and describe whether the article provides supporting or contrasting evidence. scite is used by students and researchers from around the world and is funded in part by the National Science Foundation and the National Institute on Drug Abuse of the National Institutes of Health.